ETI 7200 Series Modular,
Redundant DC Power Systems
Rugged Rack or Fixed Mount DC Power Systems
Hot Swappable Input and Output Power Modules
Single, N+1 or Full Redundancy Configurations
The field provenETI 7200 Series is ideally suitedfor military, industrial, medical and telecommunications applications requiringhigh reliability DC power. The rugged design is suitable for rack, vehicular or fielddeployable installations, yet is compact and lightweight.
If you need high-density, modular, N+1 hot swap power supplies, The ETI 7200 Series provides the ultimate inversatility with an MTBF in excess of 1 million hours and field-upgradeable configurations from 200 watts to 7.2kW. The heavy-duty chassis, occupying only 5.25”(3U), has rounded metal corners and rugged handles, aiding in safe handling. Internally, all major components are wellsecured and electrically insulated to prevent damage due to shock andvibration. The EMI/RFI filtersand input power factor correction minimize both input current and harmonics. The LED arrays keep the operatorinformed as to the unit's status.
Overall, the ETI 7200 Series is uniquely qualified for criticalshipboard, vehicle, airborne or land based systems combining advanced modular designfeatures with highly reliable construction.
CUSTOM POWER SUPPLIES FROM OFF-THE-SHELF COMPONENTS:
At the heart of the ETI 7200 Series is a complete selection of standard off-the-shelf HDC modules with different combinations of input voltages, output voltages, currents and system interface signals. This allows you to tailor a power supply to your specific needs without the high costs associated with custom designs.
FAST-TURN PROTOTYPING:
Unlike typical custom power supply projects which take massive amounts of money, manpower and time, an ETI 7200 prototype can be configured and available in just a few short weeks.
UP TO 30 OUTPUTS AT A VARIETY OF CURRENTS:
Our unique modular approach allows you to configure your power supply with up to 30 separate outputs in virtually any combination of voltages and currents. Extra wide trim ranges of +10 to -30% allow you to adjust standard outputs to any voltage between 0 to 72 VDC per LRU.
N+1 HOT-SWAP, FAULT-TOLERANT DESIGN:
If your requirement calls for dual redundancy, triple redundancy or more, we've got you covered. Our front-panel-control N+1 line replaceable units (LRUs) allow you to configure your power supply with the redundancy level and parallel operations you need.
COMPLETE CONTROL, MONITORING AND REMOTE SENSING:
The ETI 7200 LRU is available with your choice of front-panel on/off Switch, Status Monitor LED, Test Points and/or Remote Voltage Adjustment. All outputs feature remote sensing capability.
WORLDWIDE INPUT VOLTAGES:
Wherever your project takes you, we have the input voltage you need. Universal power factor corrected AC front ends of 85-265 VAC (using 600 watt modules) allow you to configure a product capable of being utilized anywhere in the world. If you prefer, DC input voltages of 24, 28, 48 or 380 VDC are available with tolerance ranges allowing virtually any other voltage in between.
RUGGED, COMPACT RACKMOUNT PACKAGE:
The ETI 7200 is available in both 23" and 19" rack adaptor chassis. Both chassis feature rugged, industrial/military construction without sacrificing aesthetics. From the boardroom to the telecom room, the ETI 7200 is a welcome compliment to any environment.
SCALEABLE FROM 200 WATTS TO 7.2 KW:
Your system's power and control needs are likely to change over time. Don't worry. We designed the ETI 7200 Series to be scaleable from 200 watts to as much as 7200 watts. Most upgrades can be predesigned or field implemented.
INPUT:
NOMINAL INPUT VOLTAGE |
INPUT RANGE (Select One Only) |
28 VDC
48 VDC
200 VDC |
20-32 VDC
36-72 VDC
220-400 VDC |
100, 120, 220, 230
240, 250, 260 VAC |
85-265 VAC
(Using 600 watt modules) |
208, 220, 230, 240
250, 260 VAC |
174-265 VAC
(Using 1000 watt modules) |
OUTPUT:
DC-DC MODULE
OUTPUT VOLTAGE
FOOTNOTE |
QTY MODULES
PER LRU |
MAX CURRENT
AMPS / LRU |
MAX POWER
WATTS / LRU |
V-OUT ADJUST
RANGE
FOOTNOTE |
2 VDC |
1 |
60 |
120 |
1.8-2.2 |
2 |
120 |
240 |
3 |
180 |
360 |
3.3 VDC |
1 |
50 |
165 |
3.0-3.6 |
2 |
100 |
330 |
3 |
150 |
495 |
5 VDC |
1 |
40 |
200 |
4.5-6.0 |
2 |
80 |
400 |
3 |
120 |
600 |
8 VDC |
1 |
30 |
240 |
7.0-9.0 |
2 |
60 |
480 |
3 |
90 |
720 |
12 VDC |
1 |
20 |
240 |
10.8-13.2 |
2 |
40 |
480 |
3 |
60 |
720 |
15 VDC |
1 |
16 |
240 |
13.5-16.5 |
2 |
32 |
480 |
3 |
48 |
720 |
24 VDC |
1 |
10 |
240 |
21.6-26.4 |
2 |
20 |
480 |
3 |
30 |
720 |
28 VDC |
1 |
9 |
250 |
25.2-30.8 |
2 |
18 |
500 |
3 |
27 |
750 |
AC-DC MODULE
OUTPUT VOLTAGE |
QTY MODULES
PER LRU |
MAX CURRENT
AMPS / LRU |
MAX POWER
WATTS / LRU |
380 VDC |
(1) 600 watt |
1.5 |
600 |
(2) 600 watt |
3.0 |
1200 |
(1) 1000 watt |
2.5 |
1000 |
(1) 1000 watt |
5.0 |
2000 |
Overcurrent Protection |
110-120% Full Load, Auto Recovery |
Current Share |
Automatic |
Power Fail |
Visual / Output Signals Available |
MTBF (MIL-HNDBD-217E) |
1M+ Hours on HDC |
OVP |
105%-130% (Non Shutdown, Auto Recovery) |
Current Limit |
115% (Auto-Recover) |
Operating Temp |
-40deg C to 100deg C Module Case |
Ripple |
</-5V=/<3%, >/-5V/<0.5Vp-p |
Remote Sense Comp. |
0.5V Total |
Trim Range V1 (DC) |
+or- 10% |
Topology |
Modular HDC |
Transient Response |
400 micro secs |
Efficiency |
75% Min @ Full Load |
Line Regulation |
0.5% Max (0.2% Typ) |
Load Regulation |
1.0% Max (0.5% Typ) |
Safety Agency |
DTM: UL, CSA, VDE, IEC |
Input Frequency |
27-70Hz (440Hz Optional) |
Power Factor |
.99 |
Harmonic Distortion |
<5% Peak Typical |
Output Voltage |
380 VDC |
Efficiency |
90/94 % (120/240 VAC) Typical |
Inrush Limiting |
<15A Peak Typical |
Short Circuit
Protect Trip Point |
1.8A (Auto Recovery) |
Thermal Protection |
105-110deg C (Auto Recovery) |
Auxiliary Supply |
14V @ 10ma |
Operating Temp |
-40deg C to +100deg C Module Case |
DC OK Signal |
Power Fail Sig. @ <355 VDC |
Load Enable |
Direct Link w/PMA Logic |
Overvoltage Protection |
415 VDC Non-Shutdown |
Thermal Resistance |
3.3deg C / with Case / Ambient |
Isolation |
Input/Output: Non-Isolated
Input/Output: Case 2500 VDC |
Holdup Time |
20 ms Min @ Full Load |
Safety Agency |
DTM: UL, CSA, VDE, IEC |
FOOTNOTES:
1) Modules can be configured to provide other voltages. Contact factory for details.