Part Number:
ETI0001-2258
NSN: 6130-01-518-4664
Rugged Mil Spec® Rack or Fixed Mount
1500 VA UPS and Frequency Converter
Canadian Navy Standard Product
1.5 kVA Mil Spec UPS and Frequency Converter
Rugged Rack or Fixed Mount Unit
w/ Reduced Depth and Removable Battery Module
ETI0001-2258 Rugged Mil Spec UPS Standard Front Panel Layout
ETI0001-2258 Rugged Mil Spec UPS Standard Rear Panel Layout
The field proven Military Power® UPS line is ideally suited for military,industrial, computer and telecommunications applications requiring high reliability, ruggedconstruction, compact size and light weight design. These units are equallysuited for use in shipboard, airborne, vehicular, field deployed or fixedlocations with controlled or uncontrolled environments. The"
ETI0001-2258" is being used by the Canadian Navy becauseof their stringent performance and reliability requirements.
The heavy-duty chassis,occupying only 7" (4U) of rack space and 18.5" depth, has rounded metal cornersand rugged handles front and rear, aiding in safe handling. Internally, all majorcomponents are well secured and electrically insulated to prevent damage due to shock andvibration.
The internal shieldedinput transformer provides galvanic isolation with provisions for domestic (115 VAC, CONUS) and optionally for international (230 VAC, OCONUS) inputvoltages. Special EMI/RFI filters and inputpower factor correction minimize both input current and harmonics. The unit also operatesas a frequency converter, taking 46-70 hertz input and converting it to clean,uninterruptible 60 hertz power. The input switch and the galvanic isolationtransformer all provide a double pole isolated source for all installations including shipboardsystems or overseas locations where phase references and grounding are notconsistent.
The LED arrays keep theoperator informed as to the unit's status including load and battery levels. Thehigh intensity audible alarm can be heard in high noise environments. All controlsand protective devices are brought to the front and rear panels with critical switches having fingerguards. Further, all front panel devices are recessed to prevent damage or accidentaloperation. Variousoptional power distribution controls are available which mount on the front panel orremotely.
The rear panel provides locking connectors for the input and outputpower. Multipleinput and output power panel options are available. Removable and washable air filters and a high capacitystainless steel ball bearing fans provideadded protection in both controlled and hostile environments. The exhaust air is diverted out therear vent, with alternateair flow directions optional. The "
ETI0001-2258" has the added benefit of having afield replaceable battery via a rear drawout battery module. The batteries are maintenance free with immobilized electrolyte and areconstructed of flame retardant materials. For more information, see the BatteryTechnology section. The Status connector provides aninterface with optional computer software providing loss of AC and low battery status as well asremote shut down capability.
See the Power Distribution Units section for alisting of stand alone PDUs. See the N5 Series
ETI0001-1482for a version of this UPS with an integrated PDU and remote control.
Overall, the MilitaryPower line is uniquely qualified for criticalshipboard, vehicle, airborne or land based systems combining advanced modular designfeatures with highly reliable construction.
AC OUTPUT | |
Output voltage: UPS | 120 VAC true sinewave standard, up to 600 VAC optional |
Output rating: UPS | 1500 VA standard in 4U x 18.5" deep 0.65-0.75 pf standard, optional configurations to 24,000 VA |
Non-linear load capacity: UPS | Up to 100% non-linear load capability w/o derating |
Output voltage regulation: UPS | ± 3.0% static regulation of nominal ± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: UPS | 110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: UPS | Less than 5.0% into 100% non-linear load |
Output frequency: UPS | 60 Hz ± 1.0% independent of input frequency 50, 400 or 1000 Hz output available as an option |
Operational status | Status, load and battery LEDs, w/contacts Adjustable level,+90 dB audible alarm w/on/off |
AC INPUT | |
Input voltage selection: | Nominal 115 VAC, optional autoranging input of 85-270 VAC |
Input voltage tolerance: UPS | 85-135 VAC @ full load without using battery, to 70 VAC @ 75% load |
Input frequency: | From 46 Hz to 70 Hz standard, optional up to 440 Hz input |
Input power factor: | Better than 99% typically |
Input/output isolation: | 2000 VA, up to 120 dB common mode, <1.0 mA leakage |
Input transient suppression: | Complies with IEEE 587 and UL 1449 |
Input control/protection: | Guarded 2 pole switch w/ fuse, optional breaker Optional cold start to turn on w/o AC present |
Input power connection: | MS 3102A-22-2P, 3 pin, threaded locking |
INTERNAL BATTERY | |
Internal battery type: | Maintenance free immobilized electrolyte, Flame retardant materials (Oxygen Index 28+) |
Internal battery life: | Rated for continuous service life of 5 years |
Internal DC protection: | Front panel mounted fuse standard, breaker optional |
Internal battery time: | 15+ minutes @ 100% load, 35+ minutes @ 50% |
Internal battery recharge: | Recharged to nominal in <8 hours |
Internal battery replacement: | Drawout/plug-in module from front of unit |
DISTRIBUTION PANEL | |
Output circuits: | Two outputs standard, optional configurations |
Output control: | Optional remote control panel w/rocker switches |
Output receptacles: | Metal shell AMP 208497-1 MCPC, 3 pin locking, other options |
MECHANICAL | |
Dimensions ( H x D x W ): | 7.0 (4U) x 18.5 x 19.0 in (178 x 470 x 483 mm) |
Rack Slide Mount Patterns: | Jonathan, General Devices patterns, others optional |
Alternate Mounting Options: | Table, Wall, Floor, Portable, Horizontal/Vertical |
Unit weight: UPS w/o Battery Internal Battery Module |
95 lb. (43 kg) UPS with lift handles front and rear 64 lb. (29 kg) Battery |
Audible noise: | Less than 47 dB @ 5.0 ft., ANSI "A" scale |
Cooling type: | High capacity, positive pressure, forced air |
Cooling air direction: | Front intake, exhaust to rear, others optional |
Air intake filter: | Washable metal filter media, others optional |
ENVIRONMENTAL | |
Storage temperature: | -40° to 158° F ambient (-40° to 70° C) with fully charged batteries |
Operating temperature: | -4° to 131° F ambient ( -20° to 55° C), lower/ higher optional |
Operating humidity: | 0 to 95% relative humidity (non-condensing) |
Storage elevation: | Up to 40,000 ft (12,192 m) |
Operating elevation: | Up to 15,000 ft (4,572 m), higher optional |
STANDARDS | |
United States: | Meets UL-1778 standard for UPS equipment, MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000 |
Canada: | CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: | EMI/RFI FCC Part 15, Class A; EN55022; MIL STD 461 |
OPTIONAL ACCESSORIES | |
Autoranging International Input, Cold Start, Emergency Power Off, Elapsed Time Meter, Alternate I/O Configurations, Dual Source Input, Battery Expansion, Batteryless Operation, Battery Charger/Conditioner, Power Distribution Units, Software Interface, Asynchronous serial COM port, 10BaseT Ethernet SNMP/HTTP port, Transport Cases, Slides and Mounting Kits |